It has a surge current of 17A for 25ms repeatable every 2 seconds at 60 deg. Celsius on each point and it has a surge of 35A per common for 10ms.
|
1746-OAP12 Description:
|
module has a total output current of 9A at 30 deg. Celsius (86 deg. Fahrenheit) and it has a voltage loss of 1.2V DC at 2.0A.
|
Additionally, it provides an isolation as one group of output channels may still continue to operate even if the fuse of the other channel group is busted.
|
has Twelve (12) output channels with Six (6) points per common with each common installed with an electronic fuse.
|