known as a Sequence of Events module, where event times are reported in either UTC (universal time coordinated) or CST (coordinated system time) format. The sequence of events modules timestamps information in under a millisecond.
|
1756-IB16ISOE Description:
|
It also provides basic ON/OFF detection, a feature common to other ControlLogix modules.The operating voltage range of this module is from 10 to 55V DC with a nominal input voltage of 24V DC and a voltage category of 24/48V DC sink/source.
|
It has a current draw of 320 mA at 5.1V and 2mA at 24V, with a total backplane power of 1.7W. The thermal dissipation of this module is 17.22 BTU/hour while power dissipation is 5.5 W at 60 Degrees Celsius.
|
This feature will register a time in relation to a change in the input data. All of this occurs on a per-point basis.
|