Control mode
|
3504 temperature meter (Eurotherm, UK),
1: High-precision temperature meter, LCD liquid crystal display, 5-digit numerical display, simple configuration through quick setting, and C / F unit switching.
2: 50 groups of programs with 500 steps, power off or shutdown, restart the program can be set to start the program from the power off or starting point, and also has the functions of running, pause, skip, stop, reset and so on.
3: Standard 3 groups of PID parameters (optional 8 groups of PID parameters), with built-in PID self-tuning function.
4: Math / logic operation, timer function, alarm function, do math and logic operation function, such as automatic / manual switching of sensor and infrared sensor, high temperature furnace logic control function, and related alarm strategies and functions
5: Recipe function, different products can call different parameters
6: Customer-defined screen function, displaying current value, set value, output%, program running status and time, etc.
7: Support various communication interfaces Modbus, Ethernet, Profibus, Devicenet, can be integrated with any PLC or higher-level system
8: OEM password function
9: Multilingual support (English, French, German, Spain, Italy)
10: PC version of iTools graphical configuration software, easy to configure, monitor and debug
|
Trigger
|
Phase-shift triggering (with soft start and current limit)
Current limiting function: Regardless of how to adjust the heating time, the secondary current of our electric furnace after passing through the transformer is limited to 160A, which protects the equipment to a limited extent. No matter how you operate, the equipment will not burn out.
Soft-start function: The current will gradually increase when starting up, and the impact on the heating element is small, which is conducive to the extension of the life of the heating element.
|