Water Cooled 2250kva 4016 Series Big Power Generator Standby Power 2500 kva Generator Perkins
The Perkins® 4000 Series family of 6, 8, 12 and 16 cylinder diesel engines was designed in advance of today’s uncompromising demands within the power generation industry and includes superior performance and reliability. The 4016-61TRG3 is a turbocharged, air-to-water chargecooled, 16 cylinder diesel engine. Its premium design and specification features provide economic and durable operation as well as exceptional power to weight ratio, improved serviceability, low gaseous emissions, overall performance and reliability essential to the power generation market. The 4016-61TRG3 is specially tuned for improved load acceptance response in standby duty.
Output Ratings
Phase Rating, 50Hz, PF 0,8
Voltage
|
Standby Rating (ESP)
|
Prime Rating (PRP)
|
kVA
|
kW
|
kVA
|
kW
|
400/230
|
2500
|
2000
|
2250
|
1800
|
Diesel Engine Specifications
Powered by UK engine 2250kva super silent diesel generator price with 4016-61TRG3
Engine Model
|
4016-61TRG3
|
Engine manufacturer
|
Perkins
|
Number of Cylinders
|
16 cylinders
|
Cylinders arrangement
|
Vertical in line
|
Cycle
|
4 stroke
|
Aspiration
|
Natural
|
Bore×Stroke
|
160mm x190mm
|
Displacement
|
61.1L
|
Compression ratio
|
13:1
|
Standby Power/Speed
|
2183kWm / 2925hp
|
Speed Governor
|
Electrical
|
Cooling System
|
Forced water cooling cycle
|
Steady speed droop
|
≤1%
|
Total lubrication system capacity
|
237L
|
Coolant capacity (engine only)
|
260L
|
Starter Motor
|
DC24V
|
Alternator
|
DC24V
|
Alternator Specifications
Alternator brand
|
Stamford, Marathon, Leroy Somer, Mecc-alte, TWGII…
|
Prime power
|
2250kva
|
Frequency/speed
|
50HZ
|
Exciter type
|
Brushless
|
Power factor
|
0.8
|
Voltage adjust range
|
≥5%
|
Voltage regulation NL-FL
|
±0.5%
|
Insulation Grade
|
H
|
Protection Grade
|
IP23
|
2250kva diesel generator (Control panel)
Brand
|
Deepsea/ComAp
|
The control module gives digital readouts of:
Generator voltage;
Output frequency;
Engine speed;
Battery voltage;
Engine hours run.
The control module has indicators for failure
information:
Overspeed/underspeed,
Emergency stop
Low oil pressure;
High water temperature
Failure to start
Battery charger failure
Automatic shutdown occurs under:
Low engine oil pressure;
High engine water temperature;
Overspeed/underspeed;
Failure to start after three attempts.
|
Perkins Standby Generator 2000KW/2500KVA 4016-61TRG3 Photos
-
24 hours continuous stable power supply, in extreme or normal temperatures from -10 °C to 50 °C.
AI Power generators are design to work 24*7 in extreme temperature conditions with minimum maintenance requirement.
-
In some cases CHP & CCHP (Combined heat and power/ Combined cooling heat and Power) to utilized heat.
AI Power specially designs Diesel and Gas CHP/CCHP Power generators to provide hot water or steam as well as Power.
-
Lower noise level is important.
AI power generators are made to be environment friendly with low emission and lower noise level
-
Reliable AMF & ATS System (Auto mains failure & Auto transfer System) which can start and stop generators automatically with load transfer in case of city supply on or off.
More information Feel Free To Contact Us At Any Time
Have a nice day !
Ms.Nancy Huang
Xiamen Ai Power Technology Co.,Ltd.
Power system supplier-Generator sets, Lighting Tower, Reefer Genset
Add:Room 702,No.581 Hengtian Road,Jimei District,Xiamen City,China
Email: nancy@aipowergen.com |
www.aipowergen.com
Skype: nancy19830320
Tel/WhatsApp/Wechat: +86-1390 6008 114