30.1kw High Efficiency Air Cooled Style Industrial Chiller ACK-10(D)

Air-cooled chiller systems typically have a lower first and maintenance cost since they do not require a cooling tower, water pumps, and associated condenser water chemical treatment. In addition, we can accept OEM.




30.1kw High Efficiency Air Cooled Style Industrial Chiller ACK-10(D)

 

Specification

Model Item

ACK-10(D)

nominal cooling capacity

kcal/h

25886

kw

30.1

input power

kw

10.52

power supply

3PH  380V  50HZ

refrigerant

type

R22(R134A/R407C/R410A)

type of control

 expansion valve

compressor

type

hermetic scroll type

power(kw)

8.1

condenser

type

finned copper tube+low noise outer fan 

power(kw)

0.92

cooling air flow(m3/h)

10000

evaporator

type

shell and tube+water tank

chilled fluid flow(m3/h)

5.19

 volume(L)

85

inlet and outlet pipe diameter(inch)

1-1/2

pump

power(kw)

1.5

lift(m)

20

safety protection

compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection

weight

kg

500

dimension

mm

1530*780*1630

Note: 1.Nominal cooling capacity is according to:

      Inlet chilled fluid temperature: 17℃

      Outlet chilled fluid temperature: 12℃

      Inlet cooling air temperature: 30℃

      Outlet cooling air temperature: 35℃

    2. Working Range:

      The temperature range of chilled fluid is from 5℃ to 35℃;

      Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.

      It is better to run the chiller while the ambient temperature at or below 35℃.

     We reserve the right to modify the above dimensions or parameters without further notice.

 