Product Description:
S800 I/O provides distributed I/O on PROFIBUS and Advant Fieldbus 100
(AF100). S800 I/O is also used as a communication link to some of ABB’s Drives.
With the network definition PROFIBUS, it means the both versions;
PROFIBUS-DP and PROFIBUS-DPV1.
An I/O station can be configured over the Fieldbus. Typical parameters are signal
range, filter time, etc.
The status of the modules are indicated by LEDs and also accessible over the
fieldbus. Analog values are scaled 0-100% of the signal range. AI/AO modules are
scanned every 4th I/O scan cycle. RTD/TC every 10th cycle.