Air Cooled Water Chiller China Manufacturers ACK-20(D)
Specification
Model Item
|
ACK-20(D)
|
nominal cooling capacity
|
kcal/h
|
51772
|
kw
|
60.2
|
input power
|
kw
|
19.96
|
power supply
|
3PH 380V 50HZ
|
refrigerant
|
type
|
R22(R134A/R407C/R410A)
|
type of control
|
expansion valve
|
compressor
|
type
|
hermetic scroll type
|
power(kw)
|
16.2
|
condenser
|
type
|
finned copper tube+low noise outer fan
|
power(kw)
|
1.56
|
cooling air flow(m3/h)
|
20000
|
evaporator
|
type
|
shell and tube+water tank
|
chilled fluid flow(m3/h)
|
10.38
|
volume(L)
|
170
|
inlet and outlet pipe diameter(inch)
|
2
|
pump
|
power(kw)
|
2.2
|
lift(m)
|
20
|
safety protection
|
compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection
|
weight
|
kg
|
950
|
dimension
|
mm
|
2150*1130*1820
|
Note: 1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
It is better to run the chiller while the ambient temperature at or below 35℃.