MODEL
|
PDF-600-C12
|
PDF-600-C24
|
PDF-600-C48
|
OUTPUT
|
DC Output
|
12V
|
24V
|
48V
|
Rated Current (90~175Vac)
|
35A
|
20A
|
10A
|
Rated Current (176~264Vac)
|
50A
|
25A
|
12.5A
|
Ripple and Noise
Note 2
|
0-70℃
|
≤120mV
|
≤150mV
|
≤480mV
|
-20-0℃
|
≤240mV
|
≤240mV
|
≤480mV
|
Voltage ADJ. Range
|
11.8~13.2V
|
23.4~26.4V
|
47.5~52.8V
|
Voltage Accuracy
|
±3%
|
±2%
|
Line Regulation
|
±1%
|
±0.5%
|
Load Regulation
|
±2%
|
±1.0%
|
Set-up Time
|
≤2S (220Vac input, Full load)
|
≤2.5S/110Vac ≤1.5S/220Vac
, full load
|
Hold up Time
|
≥10mS /(220Vac input, Full load)
|
Temperature Coefficient
|
±0.03%/℃
|
Overshoot and Undershoot
|
<5.0%
|
INPUT
|
Voltage Range
|
90Vac~264Vac
|
Frequency Range
|
47Hz--63Hz
|
Power Factor(Typical)
|
PF>0.95/220Vac, full load
|
>0.98/110Vac >0.95/220Vac full load
|
Efficiency ( Typical) @220Vac
|
90%
|
91.8%
|
93.8%
|
AC Current (max.)
|
<5A
|
<6A
|
Inrush Current (Typical)
|
<40A@220Vac Cold start
|
<15A/110Vac <30A/220Vac cold start
|
Leakage Current
|
Input—output: ≤0.25mA Input—PG: ≤3.5mA (264Vac, 63Hz)
|
Standby power consumption
|
<5W
|
PROTECTION
|
Over Load
|
52.5~65A
|
26.25~32.5A
|
|
Protection
type: 12V: Intermittent working, working time>0.1s, recovery time >2s
24V /
48V: Hiccup mode, auto recovery
|
Over Voltage
|
13.6~16V,
|
28~32V
|
54~60V
|
Protection type: Constant voltage, auto recovery
|
Over Temperture
|
95℃+5℃(detect on
thermal protector on PFC mosfet);shut down,auto recovery after the
temperature goes down to 40℃
|
Short Circuit
|
Long-term mode, constant current, auto
recovery
|
ENVIRONMENT
|
Operating amb. Temp. & Hum.
|
-20℃~70℃; 20%~90%RH No condensing (refer to
derating curve)
|
Storage Temp. & Hum.
|
-40℃~85℃; 10%~95%RH No condensing
|
SAFETY
&EMC
(Note 3)
|
Safety Standards
|
UL60950-1 2nd Ed; IEC 60950-1:2005(2nd Ed) ;EN60950-1:2006
|
Withstand Voltage
|
Primary-Secondary:3.0KVac/10mA .Primary-PG:1.5KVac/10mA.
Secondary-PG:0.5KVdc/10mA.
|
Isolation Resistance
|
10M ohms
|
EMI Conduction & Radiation
|
Compliance to EN55022, FCC PART
15 CLASS B
|
Harmonic Current
|
Compliance to EN61000-3-2,
class D
|
EMS Immunity
|
Compliance to
EN61000-4-2,3,4,5,6,8,11; heavy industry level
|
OTHERS
|
MTBF (MIL-HDBK-217F)
|
More than 200,000Hrs (25℃,
Full load)
|
Dimension (L*W*H)
|
218*116.5*40.7mm
|
Packing
|
6PCS/CTN, 8.0KGS, 0.04CBM
|
Cooling method
|
Fored air cooling(Built-in DC Fan, controlled by temperature
and load)
|
12V:
Fan working: temperature controller up to 55±10℃or Output Current >17-22A
Fan stop working: temperature controller down to 40±10℃or Output Current<15-20A
24V /48V:
Fan working: temperature controller up to 55±10℃or Output Current > 40%~60% of rated current
Fan stop working: temperature controller down to 40±10℃or Output Current<30%~50% of rated current
|
NOTE
|
1.All parameters NOT
specially mentioned are measured at rated input, rated load and 25℃of ambient temperature.
2.Measured at 20MHz of
bandwidth by using a12”twisted pair-wire terminated with a 0.1 uF & 47uF parallel capacitor.
3.The power supply is considered as a
component which will be installed into a final equipment. The final equipment
must be re-confirmed that it still meets EMC directives. For guidance on how
to perform these EMC tests, please refer to “EMI testing of component power
supplies” on https://www.powerld.com.
|