Ø Universal AC input (90~264Vac)
Ø Built-in active PFC function, PF>0.96
Ø Using ZVS technology to reduce power dissipation
Ø Built in Fan speed control and over temp. protection
Ø Built in AC inrush current limiting circuit(<20A)
Ø Build in constant current limiting circuit
Ø Built in Remote Sense Function
Ø Build in DC OK signal
Ø Wide operating ambient temperature (-30℃~70℃)
Ø Output protection: OLP/OVP/SCP/OTP
Ø PCB soldering side with conformal coating
Ø 1 U low profile,41mm
Ø 3 years warranty
MODEL
|
PDF-600-12
|
PDF-600-24
|
PDF-600-36
|
PDF-600-48
|
OUTPUT
|
DC Output
|
12V
|
24V
|
36V
|
48V
|
Rated Current
|
42A
|
26.5A
|
17.5A
|
13.6A
|
Current range
|
0~42A
|
0~26.5A
|
0~17.5A
|
0~13.6A
|
Ripple and Noise
Note 2
|
0-70℃
|
≤150mV
|
≤150mV
|
≤150mV
|
≤200mV
|
-30℃
|
≤150mV
|
≤150mV
|
≤150mV
|
≤200mV
|
Voltage ADJ. Range
|
11.5~12.8V
|
21~27V
|
33~38V
|
40~52V
|
Voltage Accuracy
|
±5.0%
|
±1.0%
|
±1.0%
|
±1.0%
|
Line Regulation
|
±0.5%
|
±0.5%
|
±0.2%
|
±0.5%
|
Load Regulation
|
±2.0%
|
±1.0%
|
±0.5%
|
±1.0%
|
Set-up Time
|
≤3S /220Vac input, Full load) ; ≤5S /115Vac input, Full load)
|
Hold up Time
|
≥10mS / (220Vac input, Full load)
|
Temperature Coefficient
|
±0.05%/℃
|
Overshoot and Undershoot
|
<5.0%
|
INPUT
|
Voltage Range
|
90Vac~264Vac
|
Frequency Range
|
47Hz--63Hz
|
Power Factor(Typical)
|
PF≥0.96/230VAC PF≥0.98/115VAC (Full Load
)
|
Efficiency ( Typical) @220Vac
|
84%
|
89%
|
90%
|
90%
|
AC Current (max.)
|
7A/115VAC,5A/230VAC
|
Inrush Current (Typical)
|
<20A@230Vac Cold start
|
Leakage Current
|
Input—output: ﹤0.25mA@264Vac ; Input—PG: ≤1mA/240VAC
|
PROTECTION
|
Over Load
|
46.2~56.7A
|
29.15~35.775A
|
19.25~23.625A
|
14.96~18.36A
|
Protection type: Constant current, auto recovery
|
Over Temperature
|
105℃+5℃(detect
on Mosfet temperature);shut down,auto recovery after the temperature goes
down to75℃
|
Over Voltage
|
13.2~15.6V
|
27.6~36V
|
41.4~48.6V
|
52.8~72V
|
Protection type: Constant voltage
|
Short Circuit
|
Long-term mode, constant current, auto
recovery
|
ENVIRONMENT
|
Operating amb. Temp. & Hum.
|
-30℃~70℃; 20%~90%RH No condensing (refer to derating curve)
|
Storage Temp. & Hum.
|
-40℃~85℃; 10%~95%RH No condensing
|
SAFETY
&EMC
(Note 3)
|
Safety Standards
|
UL60950-1 2nd Ed; IEC 60950-1:2005(2nd Ed) ;EN60950-1:2006
|
Withstand Voltage
|
Primary-Secondary:3.0KVac/10mA .Primary-PG:1.5KVac/10mA.
Secondary-PG:0.5KVdc/10mA.
|
Isolation Resistance
|
100M ohms
|
EMI Conduction&Radiation
|
Compliance to EN55022, EN55024,
FCC PART 15 CLASS B
|
Harmonic Current
|
Compliance to EN61000-3-2, class
D
|
EMS Immunity
|
Compliance to
EN61000-4-2,3,4,5,6,8,11;
|
OTHERS
|
MTBF (MIL-HDBK-217F)
|
More than 200,000Hrs (25℃, Full load)
|
Dimension (L*W*H)
|
12V: 226×116.5×41mm;
others: 218*116.5*41mm
|
Packing
|
6PCS/CTN, 8.7KGS, 0.04CBM
|
DC OK signal
|
4~6V
|
Cooling method
|
Fored air cooling(Fan speed controlled by load and internal
temperature)
|
NOTE
|
1. All parameters NOT
specially mentioned are measured at rated input, rated load and 25℃ of
ambient temperature.
2. Measured at 20MHz of
bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uF &
47uF parallel capacitor.
3.
The power supply is considered as a component which will be installed into a
final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer
to “EMI testing of component power supplies” on http://www.powerld.com.
|