Contact me to get the best price:
sales7@amikon.cn 86-18965423501 86-18965423501 AMKPLC
Products Detail:
Brand
|
PROSOFT
|
Part Number
|
MVI69-MNET
|
Product Type
|
Modbus TCP/IP Enhanced Communication Module
|
Payment
|
T/T,100% advance payment
|
Shipping Port
|
Xiamen,China
|
Lead Time
|
In stock
|
The MVI69-MNET module is designed for use with 1769 series processors, with specific power supply distance ratings and limitations for different processors. For 1769-L23x processors, note the following power consumption details:
1769-L23-QBFC1B: Consumes 800 mA at 5 Vdc. The MVI69-MNET module will use all of the available power, leaving no room for additional modules on this processor.
1769-L23E-QB1B: Provides 1000 mA at 5 Vdc. The MVI69-MNET module consumes 800 mA, allowing one additional module to be used, as long as it consumes less than 200 mA at 5 Vdc.
Software Requirements:
Automation Software: RSLogix 5000 or RSLogix 500 (for MicroLogix) programming software.
RSLinx Communication Software.
PC Requirements: A Pentium® II 450 MHz minimum, with Pentium III 733 MHz (or better) recommended.
Graphics: 256-color VGA graphics adapter with a minimum resolution of 800 x 600.
RAM: Minimum 128 MB of RAM, with 256 MB recommended.
Storage: Sufficient hard disk space (at least 100 MB or more based on the application).
CALL US: