Models 3502E, 3503E, and 3505E can self-test to detect stuck-ON conditions where the circuitry cannot tell whether a point has gone to the OFF state. Since most safety systems are set up with a de-energize-to-trip capability, the ability to detect OFF points is an important feature. To test for stuck-ON inputs, a switch within the input circuitry is closed to allow a zero input (OFF) to be read by the optical isolation circuitry.
IAI RCS-SM-I-100-H-350-S
RCS-SM-I-100-H-350-S | IAI | Industrial Supply
sales3@amikon.cn
The last data reading is frozen in the I/O communication processor while the test is running.
All TMR digital input modules support hot-spare capability, and require a separate external termination panel