Water Cooled Industrial Chiller Units

Water-cooled screw type low-temperature chiller is designed for refrigeration, refrigeration and industrial cooling. It requires a complete range of models to meet the requirements of different cooling capacity and temperature requirements.




Water Cooled Industrial Chiller Units


Introduction

Water-cooled screw type low-temperature chiller is designed for refrigeration, refrigeration and industrial cooling. It requires a complete range of models to meet the requirements of different cooling capacity and temperature requirements.


Cooling Consumption for reference 


  Sizing Information for 1 ton cooling Consumption 
Injection Molding  30 lbs/hr polyolefin's  50 lbs/hr polystyrene  45 lbs/hr PVC  40 lbs/hr PET
Extrusion  50 lbs/hr polyolefin's  75 lbs/hr polystyrene  65 lbs/hr PVC   
Blow Molding  40 lbs/hr polyolefin's 
Hydraulic Cooling  0.1 ton of cooling per 1 HP 

Industrial Chiller Unit for Plastic Industry 

Water Cooled Industrial Chiller Units



 

Cooling System Drawings - Industrial Cooling for Plastic Injection Machines

Water Cooled Industrial Chiller Units


Water Cooled Industrial Chiller Units


Features of Industrial Chiller for Plastic Industry

Higher Energy Efficient : COP of 12outlet water temperature higher (15~20%) than normal unit of 7outlet water temperature, means energy-saving efficient.

Oversized Condenser and Evaporator: Oversized condensers not only make for a long lasting compressor, they are also designed to operate in extreme conditions, i.e., above 45and as low as -25, or at any temperature in between.

Heat Recovery: Supplying 55free hot water, Heating Capacity approx. 1/3 of Cooling Capacity, increasing unit efficient about 5%.

Integrated System: Built in water tank and water pumps module set (with valves and strainer assemble in a module), no piping and wiring errors, simple installation, save time and labor cost.

Water Tank: For supplying a stable outlet water temperature, also supplying multiple outlet water temperature to different cooling requirements application.

Water Pumps: With pump controller making unit reliable and easy operation.

Non-rusting Water Piping: Pipes can be plastic or stainless steel with galvanized steel fittings.



Technical Parameters of Water Cooled Industrial Chiller Units 


Water Cooled Industrial Chiller Units

Notes

1. These are our standard chiller units, our factory accept produce non-standard unit according to your specification(inlet/out water temperature, power supply, refrigerant, etc.)

2. Rated Cooling Capacity Base: Chilled Water In/Outlet 17°C/12°C, Cooling Water In/Outlet: 30/35°C ,Air ambient: 35°C, fouling factor: 0.088m²·°C/KW;

3. Chilled Water Range: 5~ 20°C;

4. Cooling Water Range: 15 ~ 40°C;

5. Changes of Specification for improvement may be made without notice. 





Please contact me
 
Ann
Sales Engineer

H'Stars (Guangzhou) Refrigerating Equipment Group Ltd.
No.1 Guoyuan 4th Road,the Northern Part of the Eastern Section of Guangzhou Econmic &Technology Development District,Guangzhou,China.
Tex : +86 -20-62266755 ext 673| Fax:  +86 -20-62266081 
Mobile/WhatsApp/Wechat: +8615800240365
Web:  www.hstarschiller.cocm    www.heatexchangermaker.com     





INQUIRY

Contact us for all information about the product


click here to leave a message

leave a message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.