Product Description

The ACTUATOR OUTPUT can be stroked (or calibrated) from the SERVICE MODE. Pressing the down arrow on the hand-held programmer when the display shows WOODWARD GOVERNOR COMPANY will enter the SERVICE MODE. Pressing the ESC key will return to the Woodward heading. Press the left arrow until the VALVE header appears. Next, press the down arrow to see VALVE menu options. Continue pressing the down arrow until STROKE VLV OUTPUT? appears. Press the turtle or rabbit adjust-up arrow to change the display to TRUE. The control must be tripped to perform this function.