Category
|
Specification
|
Model
|
SAI143-HE3 S3
|
Number of Input Channels
|
16 channels, module isolation (*5)
|
Rated Input Range
|
4 to 20 mA
|
Permissible Input Range
|
0 to 25 mA
|
Data Update Frequency
|
40 ms
|
Temperature Drift
|
±16 µA/10 °C
|
Transmitter Power Supply
|
16.15 V minimum (at 20 mA), 26.4 V maximum (at 0 mA)
|
Output Current Limit
|
25 mA
|
2/4-Wire Setting
|
Individual channel setting, changed by setting pins
|
Withstand Voltage
|
1.5 kV AC between input signal and system for 1 minute (*2)
|
Maximum Current Consumption (5 V System)
|
320 mA
|
Maximum Current Consumption (24 V System)
|
550 mA
|
Support PRM
|
Available (SAI143-H)
|
Transmitter Power Supply ON/OFF Function
|
Available in 2-wire setting, for all 16 channels at the same time
|
sales7@amikon.cn 86-18965423501 86-18965423501 AMKPLC